| Range | Compact |
|---|---|
| Product range | ComPacT NSX100...250 |
| Type of product or equipment | Trigger |
| Trigger Name | Micrologic 5.2 E |
| Trigger Type | Electronic |
| Range compatibility | ComPacT NSX100 ComPacT NSX160 ComPacT NSX250 |
| Application | Distribution |
| Number of poles | 4P |
| Protected poles | 3t + N/2 3t + OSN 4t 3t |
| Position of the neutral pole | LEFT |
| Trigger protection functions | LSI |
| Type of protection | L: for overload protection (long delay) S: for short delay protection I: for instantaneous short-circuit protection |
| Nominal tripping current | 100 A at 40 °C |
| [Ue] assigned operating voltage | 690 V AC 50/60 Hz |
| Network type | THAT |
| Network frequency | 50/60 Hz |
Compact NSX100-250 - micrologic 5.2 E trip unit - 100A - 4P4d - LV429105
SKU: 3606480017001
€225.00Price
Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 positions [Ir] long-time protection pick-up adjustment range 40...100 A Long-time protection delay adjustment type tr Adjustable [tr] long-time protection delay adjustment range 15…400 s at 1.5 x Ir
0.35…11 s at 7.2 x Ir
0.5…16 s at 6 x IrThermal memory 20 minutes before and after triggering Short-time protection pick-up adjustment type Isd Adjustable 9 positions [Isd] Short-time protection pick-up adjustment range 1.5...10 x Ir Short-time protection delay adjustment type tsd Adjustable [tsd] Short-time protection delay adjustment range 0…0.4 s I²t=off
0.1…0.4 s I²t=onInstantaneous protection pick-up adjustment type Ii Adjustable [II] instantaneous protection pick-up adjustment range 1.5 to 15 x In Differential protection Without Neutral protection settings 0.5 x Ir (3t + N/2)
1 x Ir (4t)
1.6 x Ir (3t + OSN)
No protection (3t)ZSI Logical Selective Locking Zone With Local signaling Ready to operate LED flashing (green)
foroverload LED 105% Ir (red)
foroverload LED 90% Ir (orange)Display type LCD display Type of measurement Energy meter Data communication Instantaneous and demand values
Maintenance indicators
Energy measurement
Current and power demand
Maximeters/minimeters
Stamping time histories and event tables
Power quality
Protection and alarm settingsElectrical data recording Maintenance indicators