top of page
Range Compact
Product range ComPacT NSX100...250
Type of product or equipment Trigger
Trigger Name Micrologic 5.2 E
Trigger Type Electronic
Range compatibility ComPacT NSX100
ComPacT NSX160
ComPacT NSX250
Application Distribution
Number of poles 4P
Protected poles 3t + N/2
3t + OSN
4t
3t
Position of the neutral pole LEFT
Trigger protection functions LSI
Type of protection L: for overload protection (long delay)
S: for short delay protection
I: for instantaneous short-circuit protection
Nominal tripping current 100 A at 40 °C
[Ue] assigned operating voltage 690 V AC 50/60 Hz
Network type THAT
Network frequency 50/60 Hz

Compact NSX100-250 - micrologic 5.2 E trip unit - 100A - 4P4d - LV429105

SKU: 3606480017001
€225.00Price
Quantity
  • Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 positions
    [Ir] long-time protection pick-up adjustment range 40...100 A
    Long-time protection delay adjustment type tr Adjustable
    [tr] long-time protection delay adjustment range 15…400 s at 1.5 x Ir
    0.35…11 s at 7.2 x Ir
    0.5…16 s at 6 x Ir
    Thermal memory 20 minutes before and after triggering
    Short-time protection pick-up adjustment type Isd Adjustable 9 positions
    [Isd] Short-time protection pick-up adjustment range 1.5...10 x Ir
    Short-time protection delay adjustment type tsd Adjustable
    [tsd] Short-time protection delay adjustment range 0…0.4 s I²t=off
    0.1…0.4 s I²t=on
    Instantaneous protection pick-up adjustment type Ii Adjustable
    [II] instantaneous protection pick-up adjustment range 1.5 to 15 x In
    Differential protection Without
    Neutral protection settings 0.5 x Ir (3t + N/2)
    1 x Ir (4t)
    1.6 x Ir (3t + OSN)
    No protection (3t)
    ZSI Logical Selective Locking Zone With
    Local signaling Ready to operate LED flashing (green)
    foroverload LED 105% Ir (red)
    foroverload LED 90% Ir (orange)
    Display type LCD display
    Type of measurement Energy meter
    Data communication Instantaneous and demand values
    Maintenance indicators
    Energy measurement
    Current and power demand
    Maximeters/minimeters
    Stamping time histories and event tables
    Power quality
    Protection and alarm settings
    Electrical data recording Maintenance indicators
    bottom of page